Designing a Combustion Air/Gas Pre‐Mix System For Red‐Ray Infrared Process Burners
- Determine load requirements based on application (BTU/hr)
- Choose burner type based on process / application / requirements
- Determine number of burners required and configuration (number of burners per row based on oven and product constraints)
- Determine Ignition / Monitor Methods
- RP‐I / RP‐M for burners less than 4 ft
- IPQ‐1 / MPQ‐1 for burners greater than 4 ft
- UV Scanners
- IW (ignition wire) and MW (monitor wire) length (~25‐50 ft per burner)
- Mixer selection (based on 1 mixer per 1 row of burners)
- Determine mixture pressure (based on burner type) and gas volume per row (1,000 BTU/hr = 1 CFH)
- Use the Pyronics Flomixer Data Sheet to select mixer (Manufactured Gas – 1000 BTU – 0.6 Sp Gr)
- Round up to higher capacity air insert size (1/32″)
- Pyronics Flomixer – highly recommend which includes
- Manual butterfly valve
- Air Sleeve and insert combined to create suction
- Gas Adjuster valve for air/gas ratio adjustment
- Zero gas regulator (BZR)
- Gas shut‐off cock
- Flanged outlet
- Blower Selection (16 oz static pressure – LC Series 4121)
- Determine SCFHair required
- Total system load (BTU/hr) ÷ 1000 = SCFHgas
- CFHgas x 11 (11 to 1 air gas ratio) = SCFHair
- Use SCFHair to determine 16oz blower model from the Pyronics Blower 4121 Data Sheet.
- Specify blower model #, discharge position, motor HP, TEFC (total enclosed fan cover), voltage
- Select flexible sleeve with clamps (same size as blower outlet)
- Specify Air Filter
- Non‐washable Cylindrical Element
- Round Replaceable Element
- Determine SCFHair required
- Select Combustion Air Pressure Switch – (10″- 30″ w.c. range)
- Select All‐In‐One Gas Train Assembly
- Based on total CFHgas (to include all burners and pilots)
- Assembly to include
- Main shut‐off ball valve
- Main pressure regulator
- Low and high gas pressure switches
- Visual and electronic position indication switches
- Double blocking valve
- Threaded body flange
- Select Main Gas Shut‐Off Ball Valve (size based on plant gas line running to equipment)
- Select Y‐Strainer (same size as main gas ball valve)
- Add (3) ¼” NPT dial (visual) pressure gauges 0‐30″ WC with ¼” NPT ball valve (rated for gas)
- (1) use for combustion air header
- (2) use before/after All‐In‐One Train Assembly
- Control Panels – contact Red‐Ray for design and pricing
- Automated burner control
- Temperature controller
- Motorized butterfly valve – Pyronics Flanged Butterfly Motorized Package Valves 1302 Data Sheet
- For system control – size based on main air header blower outlet
- For individual burner control – size based on mixer inlet
- Temperature measuring methods
- Thermocouple probe (used to measure ambient air)
- Optical pyrometer (used to measure product temperature)